Temperature probes and transducers for Pt1000/3850ppm sensor with 4-20mA output for two-wire connection are built in a durable watertight case. Output temperature range is user adjustable. Degrees Celsius and Fahrenheit are user selectable. Large dual line LCD is an advantage. Display is possible to switch off. Computerized design ensures maximum long term stability and fail indication.
APPLICATIONS - measuring and control of temperature at:
- warehouses
- glasshouses
- manufacturers
- museums, archives, galleries
- air-conditioned rooms
- weather stations
COMMON TECHNICAL PARAMETERS |
Available temperature units: |
degrees Celsius, Fahrenheit |
Accuracy of temperature output of T0110 probe: |
±0.4°C |
Accuracy of temperature output of T4111 transducer: |
±0.15°C plus 0.1% from adjusted output span (without temperature probe) |
Temperature operating range: |
-30 to +80°C |
Temperature operating range of LCD display: |
readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
Current output - two-wire connection: |
4-20mA |
Output temperature range: |
user adjustable from the PC |
Protection: |
IP65 electronics |
Power: |
9-30Vdc |
Warranty: |
two years |
Thermometer is available in the following types:
Outputs are adjusted to maximum range from the manufacturer. Output range is user adjustable from the PC by means of the optional cable SP003 - see below. Free configuration program for transmitter adjustment is ready to download anytime. If different adjustment of temperature output range is required, please specify required output range.
Ordering example: Thermometer T4111, output -100 to +30°C
Typical application wiring
Calculation of minimum power voltage Uss for proper operation:
Uss min> Uo min + Imax * Rz,
where: Uo min= 9 V
Imax... approximately 20 mA
Rz... sensing resistor (shunt)
Included accessory of thermometer:
Traceable calibration certificate from the manufacturer, instruction manual. Calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
Example of calibration certificate.
Free program TSensor for configuring of the transmitter is ready to download.
Transmitters are directly compatible with sixteen channel Comet data acquisition system MS.
Visit also available HUMIDITY, PRESSURE TRANSMITTERS.
其它工业用变送器 >
|